Control of efficiency factor and effective power
The maximum output power as well as the efficiency factor cos (φ) can be controlled with the GridControl via remote signalling. Thus the power provider can regulate the system according to local requirements in order to ensure a reliable mains operation. Furthermore, an immediate shutoff
of the plantcan be executed.
Analogue and digital interfaces
Depending on the power supplier and the network connection point, different kinds of signals are used. The GridControl can process digital switch signals in different voltage levels. In addition, the GridControl is able to process analogue signals with common industry gauges for a remote control of the systems.
Transparency
Via the GridControl, the signals issued by the energy supply company are transferred to the monitoring system VM Touch. There, they are registered, stored and displayed in plain text.
High flexibility
The GridControl has been designed for power plants using central inverters from the VC series or thee-phase inverters from the VS series. The connection between the inverters and the VM grid control consists of a CAN-bus. For very large solar power plants, several GridControl can be combined, so the signal from the power provider does not have to be distributed.
| Each GridControl manages up to 60 inverters | |
|---|---|
| Controllable functions | GridControl (Item no. V1-122-007) |
| Limitation of plant performance through analogue or digital signals (switchable) | 0 V to 10 V; –10 V to +10 V; 0 mA to 20 mA; 4 mA to 20 mA; digital settings through 2, 3 orr 4-bit protocols |
| Setting of cos ϕ through analogue or digital signals (switchable) | 15 min. average value |
| Plant switch-off (remote) | 15 min. average value |
| General data | |
| Supply voltage | 24V DC, +/–15% |
| Power consumption | max. 15 W |
| Protection class | IP 40 according to EN 60529 |
| Permissible ambient temperature | –20 to +60 °C |
| Relative air moisture (non-condensing) | 0 to 95 % |
| Interference resistance (EMV) / Transient emissions (EMC) | DIN EN 61000-6-1, DIN EN 61000-6-2, DIN EN 61000-6-3 as well as DIN EN 61000-6-4 |
| Dimensions (WxHxD) | 185 x 240 x 120 mm |
| Weight | 1.25 kg |
| Digital inputs | |
| Input impedance | 31.32 kΩ |
| Electrical strength | 24 V |
| Screw type terminals | Up to 1.5 mm2 |
| Analogue inputs | |
| Input impedance | 22 Ω (current input), 600 kΩ (voltage input) |
| Electrical strength current input | 4 V |
| Electrical strength voltage input | 20 V |
| Screw terminals | Up to 1.5 mm2 |
| Inverter communication | |
| Interfaces | CAN Bus (2 x CAN In / 2x CAN Out), M12 circular connector, Phoenix contact |