Plant Management

GridControl

More information
Storelocator
Lupe

Interface and protocol converter for PV plants

  • Analogue and digital interfaces
  • Compatible with VC and VS series
  • Flexible wiring for large power plants 

Control of efficiency factor and effective power
The maximum output power as well as the efficiency factor cos (φ) can be controlled with the GridControl via remote signalling. Thus the power provider can regulate the system according to local requirements in order to ensure a reliable mains operation. Furthermore, an immediate shutoff
of the plantcan be executed.

Analogue and digital interfaces
Depending on the power supplier and the network connection point, different kinds of signals are used. The GridControl can process digital switch signals in different voltage levels. In addition, the GridControl is able to process analogue signals with common industry gauges for a remote  control of the systems.

Transparency
Via the GridControl, the signals issued by the energy supply company are transferred to the monitoring system VM Touch. There, they are registered, stored and displayed in plain text.

High flexibility
The GridControl has been designed for power plants using central inverters from the VC series or thee-phase inverters from the VS series. The connection between the inverters and the VM grid control consists of a CAN-bus. For very large solar power plants, several GridControl can be combined, so the signal from the power provider does not have to be distributed. 

Each GridControl manages up to 60 inverters
Controllable functions GridControl (Item no. V1-122-007)
Limitation of plant performance through analogue or digital signals (switchable)0 V to 10 V; –10 V to +10 V; 0 mA to 20 mA; 4 mA to 20 mA;
digital settings through 2, 3 orr 4-bit protocols
Setting of cos ϕ through analogue or digital signals (switchable)15 min. average value
Plant switch-off (remote) 15 min. average value
General data
Supply voltage24V DC, +/–15%
Power consumption max. 15 W
Protection classIP 40 according to EN 60529
Permissible ambient temperature–20 to +60 °C
Relative air moisture (non-condensing) 0 to 95 %
Interference resistance (EMV) / Transient emissions (EMC)DIN EN 61000-6-1, DIN EN 61000-6-2, DIN EN 61000-6-3 as well as DIN EN 61000-6-4
Dimensions (WxHxD)185 x 240 x 120 mm
Weight1.25 kg
Digital inputs
Input impedance31.32 kΩ
Electrical strength24 V
Screw type terminals Up to 1.5 mm2
Analogue inputs
Input impedance22 Ω (current input), 600 kΩ (voltage input)
Electrical strength current input4 V
Electrical strength voltage input20 V
Screw terminalsUp to 1.5 mm2
Inverter communication
InterfacesCAN Bus (2 x CAN In / 2x CAN Out), M12 circular connector, Phoenix contact



Please select a category.