Storelocator
Lupe

Pre-assembled inverter station for large-scale PV power plants

  • Fully integrated central inverter station including medium voltage transformer,
    ventilation and monitoring system
  • Available in the power classes 700 kW to 1.2 MW; graduated in 100 kW steps
  • Minimum planning, transport and installation costs
  • Optimised ventilation concept for reliable operation

Ready-for-connection comprehensive system

The new central inverter stations are pre-assembled complete solutions, available in the power classes 700 kW to 1,2 MW. They have been developed especially for the quick and error-free planning and installation of large-scale PV power plants and contain Voltwerk VC central inverters and a highly efficient medium-voltage transformer. An optional medium voltage switch gear can be integrated ex works. All connection and ventilation devices as well as the monitoring system are pre-installed and tested ex works. This allows an on-site plug & play installation.

Future-proof

The Voltwerk VIS series guarantees the operators of PV plants a maximum return throughout the entire service life. The central inverters of the Voltwerk VC series comply with all European legal norms and standards, such as the German “Medium Voltage Directive”. The entire stations is design approved and complies in dimension and lay-out with the European standard requirements.

Long maintenance intervals

Voltwerk central inverter stations reduce planning, transport and installation costs significantly. Besides the medium voltage connection, only the PV generator, a remote transmission line for the data telecommunication and any given optional components have to be connected. Moreover, the integrated ventilation system has generous airflow and filter volume reserves, which allow very long maintenance intervals.

Flexible

For project specific adjustments the stations can be fitted with various optional accessories at works. E.g. dry-type transformers are available as well as medium range switch gear.

Input values (Solar generator)
Maximum DC input voltage (Vdcmax)1,000 V
Minimum DC input voltage (Vdcmin)530 V
Maximum MPP voltage (Vmppmax)800 V
Minimum MPP voltage (Vmppmin)530 V
Maximum input current (Ipcmax)590 A (VC 300) / 400 A (VC 200) per inverter
Number of inputs4 per inverter
Fuse per input175 A - 250 A (adjustable)
Connection designM 12 bolts on copper bar
Generator junction boxIntegrated in inverter
Output data (grid)
Rated grid voltage (Vac,r)20 kV with tappings 2x +/-2,5%
Rated frequency (fr)50 Hz
Maximum frequency (fmax)65 Hz
Minimum frequency (fmin)45 Hz
Cosphi at rated capacity (cos φ)Adjustable 0.7 inductive to 0.7 capacitive
Distortion factor (at rated capacity)≤ 2 %
Connection design 7 Connection type A acc. EN 50180 and EN 50181, external cone 250A
Auxiliary supply
Required supply400 V / 50 / 14kVA / 3-phases with N / TN grid
Required pre-fusesC20 A 3 phases
Supply for customer devicesB16 A / 230 V / with RCD (one connection per inverter)
Optional auxiliary transformerDry-type transformator 400 V / 14kVA
Cooling
Cooling typeAir cooling, individually thermally controlled fan
Type of air filterPocket filter in accordance with G3 EN 779
Filter surface40 m²
Maximum counterpressure with additional station conversion50 Pa in total for feed and exhaust air
Environmental / ambient conditions
Temperature range 1–20 °C / +50 °C
Maximum temperature for permanent rated capacity 1+50 °C
Relative humidity (non-condensing)≤ 95 %
Installation altitude above sea level≤ 2,000 m
Safety / protective equipment
Protection typeIP 54 in accordance with EN 60529
Ground fault monitoringYes, with adjustable reaction type
Surge arresterIntegrated in inverter: DC-side type II. grid-side type I in accordance with IEC 61643-1
Isolation of solar generator from the gridGalvanic isolation by means of the medium-voltage transformer
Medium-voltage transformer 7
ConstructionOil transformer. hermetic design
CoolingONAN
ChargingDry and vented mineral oil
Tappings21.0 kV / 20.5 kV / 20 kV / 19.5 kV / 19 kV
Inverter
Transient emissions (EMC)DIN EN 61000-6-4:2007-09
Interference resistance (EMC)DIN EN 61000-6-2:2006-03
Equipment reliabilityDIN EN 50178:1998-04
Pre-configured standards for grid monitoringVDE 0126-1-1, ENEL, RD664, RD1663, EN50438:2007, ÖVE E 2750
Station design
Materialwu lightweight concrete LC 25 / 28 in acc. with DIN 1045:2001-07
Exposition class for exterior partsXC4, XF1, XA1 in accordance with DIN 1045:2001-07
Exposition class for interior partsXC1 in accordance with DIN 1045:2001-07
Exterior wallsWashed-out concrete, granularity 8/16 (other options available)
RoofConcrete, floating design
Foundation troughOil-proof in acc. with § 19 German Water Mgmt. (metal oil pan optional)
Exhaust air hoodAluminium
Air grilles / doors / framesHot-dip galvanised steel (optional aluminium)
Attachment points4 x Deha anchors, type 20 T
Number of cable inputsNumber, position and design depend on the project requirements
Earthing bushingHauff earthing bushing HEA-I-M12
Standards
Grid qualityDIN EN 61000-3-11:2001-04 / DIN EN 61000-3-12:2005-09
CE conformityYes
Design approvalYes (Bureau Veritas)
Conformity with German Renewable Energies Act § 6.1 EEG 2009 §6.1Yes (additional hardware may be necessary)
Conformaty with Medium Voltage Directive (BDEW) of June 2008Yes (additional hardware may be necessary)
TypeVIS 700VIS 800VIS 900VIS 1000VIS 1100VIS 1200
Article numberV1-120-07V1-120-018V1-120-019V1-120-020V1-120-021V1-120-022
AC Rated power (Pac, r) (inverter) 700 kVA800 kVA900 kVA1000 kVA1100 kVA1200 kVA
Recommended DC output (kWp)770880990110012101320
Maximum DC Power (kWp)8409601080120013201440
AC rated current (A)20.2023.1025.9828.8731.7534.64
System efficiency factor 7
Maximum efficiency factor98.1 %98.1 %98.1 %98.1 %98.1 %98.1 %
European efficiency factor97.6 %97.7 %97.8 %97.7 %97.7 %97.8 %
Californian efficiency factor97.9 %98.0 %98.0 %98.0 %98.0 %98.0 %
Auxiliary supply 2
Stand-by / nighttime performance (Pnight)330 W330 W330 W440 W440 W440 W
Power consumption (Pday) 7
Medium voltage transformer
Rated power900 kVA900 kVA900 kVA1200 kVA1200 kVA1200 kVA
Vector groupDyn5Dyn5Dyn5Dyn5Dyn5Dyn5
Short circuit voltage 66 %6 %6 %6 %6 %6 %
No-load losses 7400 W400 W400 W580 W580 W580 W

Dimensions / Weight

Dimensions (W x H x D) 52.980 x 2.980 x 6.980 mm
Weight of entire station in tons 735 t35 t35 t35 t35 t35 t

1 Depending on the operating status a derating resulting from the transformer monitoring may be possible.
2 Values at external auxiliary supply; values may vary with development condition and filter pollution grade.
3 Fans inside the station work speed-controlled.
4 Values when an external auxiliary supply is used.
5 Height specification without exhaust air hoods. Height for transport 3,25 m.
6 Typical values.
7 Exemption values when using optional accessories e.g. dry-type transformer.




Please select a category.