Single-phase string inverters with 3, 4, and 5 kW

  • Easy intstallation – 1 string per inverter
  • Highest yields – peak efficiency factor of 97.7 %
  • Wide range of applications – outdoor installation (IP 65) in temperature range of up to +60 °
  • Solar Magazin "Photon" Test: "A" for medium irradiation and "A" for high irradiation

Efficiency

Thanks to the innovative patented VTL topology, Voltwerk inverters can reach peak efficiency factors of 97.7 %. The new tech nology also ensures highest european efficiency factors of up to 97,0 %. The exceptionally fast and precise MPP tracking guarantees that there is no loss of output in case of irradiation changes.

Reliability

The new patented PowerCool cooling concept optimises heat distribution in the inverter. The sophisticated cooling sys tem and the high-quality components prevent premature ageing of the power electronics and guarantee a maximum service life expectancy for the inverters. The protection type IP 65 and the ambient temperature range of -20°C to +60°C allow an installation of the inverters in practically any environment.

Flexibility

Due to the wide input voltage range of the VS series, modules can be flexibly wired. The high input voltage (UDC = up to 940 V) permits maximum string lengths for low string losses and cost-effective photovoltaic module wiring.

Solar generator optimization

Voltwerk string inverters allow an immediate documentation of the current-voltage-curve. Thereby in particular cases wiring faults can already be determined and eliminated during commissioning on site.

Input side (PV-Generator)Voltwerk VS 3Voltwerk VS 4Voltwerk VS 5
Art.nr.V1-110-004V1-110-005V1-110-006
Recommended solar generator connected load (STC)3.2 kW4.3 kW5 kW
Maximum input voltage (Vdcmax)940 V940 V940 V
Minimum input voltage (Vdcmin)250 V250 V275 V
Start-up input voltage (Vdcstart)220 V220 V220 V
Rated input voltage (Vdc,r)700 V700 V700 V
Maximum MPP voltage (Vmppmax)750 V750 V750 V
Minimum MPP voltage (Vmppmin)250 V250 V275 V
Maximum input current (Idcmax)19 A19 A19 A
Start-up power25 Wdc25 Wdc25 Wdc
MPP tracker111
DC inputConnector, MCIV compatible (4 mm2 included in delivery, max. 10 mm2 possible)
Number of DC inputs111
MPP accuracy> 99 %> 99 %> 99 %
Output side (Grid connection)
Rated grid voltage (Vac, r)230 V230 V230 V
Maximum grid voltage (Vacmax)1264.5 V264.5 V264.5 V
Minimum grid voltage (Vacmin)1184 V184 V184 V
Maximum output current (Iacmax)14 A19 A22 A
Rated power (Pac, r)3 kW4 kW5 kW3
Maximum power (Pacmax)3 kW4 kW5 kW3
Rated frequency (fr)50 Hz50 Hz50 Hz
Maximum frequency (fmax)151.5 Hz51,5 Hz51,5 Hz
Minimum frequency (fmin)147.5 Hz47.5 Hz47.5 Hz
Power factor (cos φ)0,7 under-excited to
0,7 over-excited
0,7 under-excited to
0,7 over-excited
0,7 under-excited to
0,7 over-excited
Required grid typeTN grid / TT gridTN grid / TT gridTN grid / TT grid
Output current distortion (at rated power)≤ 3 %≤ 3 %≤ 3%
Output terminalsConnector included in delivery (flexible cable with a maxium of 6 mm2 in diameter)
Feed in typeSingle-phaseSingle-phaseSingle-phase
Stand-by consumption / nighttime consumption0.2 W0.2 W0.2 W
Efficiency factor
Maximum efficiency factor97.6 %97.7 %97.7 %
European efficiency factor96.4 %96.8 %97.0 %
Cooling
Cooling typeConvectionRegulated ventilator2
Environment requirements
Ambient temperature–20 °C / +60 °C–20 °C / +60 °C–20 °C / +60 °C
Maximum temperature for lasting rated power+50 °C+50 °C+50 °C
Relative humidity (not-condensing)0–95 % 0–95 %0–95 %
Installation altitude≤ 2.000 m≤ 2.000 m≤ 2.000 m
Site of installationindoor / outdoorindoor / outdoorindoor / outdoor
Protection / Safety
Protection typeIP 65IP 65IP 65
Protection classClass I, after IEC 62103Class I, after IEC 62103Class I, after IEC 62103
Ground fault monitoringYes (isolation measurement + RCD type B)Yes (isolation measurement + RCD type B)Yes (isolation measurement + RCD type B)
Over load behaviourWorking point adjustmentWorking point adjustmentWorking point adjustment
Over temperature behaviourDeratingDeratingDerating
Surge protection PV inputVaristors (Overload protection type 3)Varistors (Overload protection type 3)Varistors (Overload protection type 3)
Surge protection AC outputVaristors (Overload protection type 3)Varistors (Overload protection type 3)Varistors (Overload protection type 3)
Leckage current switch type B integratedYesYesYes
DC load disconnectorYesYesYes
Grid monitoring
Delay time after grid failure160 seconds60 seconds60 seconds
Trip time1< 200 milliseconds< 200 milliseconds< 200 milliseconds
Grid monitoring meets the requirementsVDE 0126-1-1 Germany, France, Greece, Benelux, RD1663 Spain, DK5940 Italy, others on demand
Dimensions / Weight
Dimensions (W x H x D) 390 x 675 x 229 mm390 x 675 x 229 mm390 x 675 x 229 mm
Weight22 kg22 kg22 kg
Conformity
Transient emissions (EMC)DIN EN 61000-6-3:2007-09DIN EN 61000-6-3:2007-09DIN EN 61000-6-3:2007-09
Interference resistance (EMV)DIN EN 61000-6-2:2006-03DIN EN 61000-6-2:2006-03DIN EN 61000-6-2:2006-03
Grid qualityIEC 61000-3-2 /-3-12 (harmonics), IEC 61000-3-3 / -3-11 (flicker)
Equipment reliabilityIEC 62109-1:2003, IEC 62109-2:2005, IEC 62103:2003 and DIN EN 50178:1998
CE conformityYesYesYes
GS approvalYesYesYes
In accordance with Renewable Energy Law 2009, § 6,1YesYesYes
In accordance with VDE-AR-N 105YesYesYes
Other
DisplayLCDLCDLCD
Communication interfaceCANCANCAN
TopologyTransformerlessTransformerlessTransformerless
Warranty5 Years, optional prolongable

1 Values for Germany; values vary according to country setting.
2 Ventilator in the devices works temperature regulated.
3 Germany Sacmax 4,6 kVA, Pac,r 4,6 kW